1. Taking Advantage of Outside Air to Reduce HVAC Costs


Depending on local climate and the amount of air being re-circulated in a building, conditioning outside air may account for a significant portion of cooling load. Spaces that can hold many people at one time such as a theater or auditorium and those that cannot recirculate air due to tasks being performed spend a lot to heat, cool, humidify or dehumidify outside air before bringing it into a building. In such cases, existing VAV control should be maximized. At some times, it may be possible to reduce air flow to a lower minimum level without violating fresh air requirements. Flow measurements and a check of the building code could yield major savings at practically no cost.

Even where most air is re-circulated, however, judicious use of outside air can help cut HVAC bills. An economizer cycle uses outdoor air instead of return air to cool a space when the outside air is significantly cooler and dryer than return air. Depending on outdoor humidity, using more outside air in the 60-65 degree range may provide some free cooling. When outside temperature is sufficiently low, below about 52-57 degrees, chillers may be shut off and 100 percent outside air used to perform all necessary cooling. Doing so may involve only changes to EMS programming or alterations to outside air damper linkage settings.

With a bit more sophisticated programming, and possibly the addition of a humidity sensor, even higher temperature outside air may be used, especially in dry climates. By comparing return air wet-bulb instead of just dry-bulb temperature to that of outside air, the differential enthalpy value is taken into account (enthalpy measures the total heat content of air, including that held by its moisture). Dry air in the high 60s may hold much less total heat than moist return air, for example. From the point of view of a cooling coil, maximum use of such outside air makes its job easier.


2.  Finding energy savings in HVAC systems

Before you start replacing expensive equipment, work with your building engineer or maintenance technician, and conduct an audit to make sure your existing equipment works properly.

Some of the simple things you may find include:

  • Variable frequency drives that were set on bypass because of a problem with the drive. We often find drives running at the full 60Hz because they have never been returned to their proper automatic action state.
  • Economizer dampers in a particular fixed position because of linkage or drive motor failures.
  • Outside air dampers with a 2x4 wedged into them to keep them open because of the same control failure as above.
  • Dirty primary or secondary filters cutting down on proper air flow.

Probably the most underexplored area, though, is thorough examination of the hydronic coils, primarily the cooling coils. Cooling coils, especially those with tight fin spacings, oftentimes act as filters, trapping not only particulate but also biological masses on the fins. This not only impedes the proper volume of air getting through the coils and thus to the spaces served by the HVAC system, but also reduces the heat transfer of the system, causing the compressors to work harder and thus use more energy. And it's the biologicals that can lead to that unpleasant "dirty socks" smell. So, proper cleaning of the cooling coils can not only save energy but also improve IAQ and IEQ. Please note the emphasis on "proper."


RELATED CONTENT:


HVAC systems , VAV , energy savings

Modine. Learn more.
Leading the way in high efficiency boilers and water heaters. Aerco, click here.


QUICK Sign-up - Membership Includes:

New Content and Magazine Article Updates
Educational Webcast Alerts
Building Products/Technology Notices
Complete Library of Reports, Webcasts, Salary and Exclusive Member Content

All fields are required.


click here for more member info.