Home of Building Operating Management & Facility Maintenance Decisions
TRENDING


Insider Reports

FacilitiesNet eNewsletter
eNews Best Information Tool For Busy FMs
We will keep you updated with trends, education, strategies, insights & benchmarks to help drive your career & project success.
Sign up for eBook




Facility Maintenance Decisions

Fire Safety: Test Systems to Comply with NFPA 72





Technicians must test system components at the required intervals and with testing methods outlined in National Fire Protection Association (NFPA) Standard 72. Testing can help confirm a range of system functions and components, including:

  • control-unit inputs and outputs
  • battery capacity
  • transmission equipment
  • system wiring
  • initiating devices
  • alarm-notification appliances
  • emergency-communications equipment and components.

Certain types of smoke and flame detectors also require special testing and calibration to verify they are operating within their listed and approved sensitivity ranges.

NFPA 72 also provides special testing criteria for heat detectors. For example, technicians must replace fixed-temperature, non-restorable, spot-type detectors after 15 years of use.

Another option is to have a laboratory test two detectors per 100 installed. If a failure occurs on any of the tested detectors, inspectors must remove and test more detectors to determine whether a general problem exists involving faulty detectors or a localized problem exists involving just one or two defective detectors.


posted on 12/30/2009

Article Use Policy



Comments