Replacing Chiller on College Campus Requires Ample Planning

By Dan Hounsell, Editor - July 2012 - HVAC


The chiller replacement actually had its roots well before 2007.

"This project really got started with the installation of the thermal-storage tank" on campus in 2000, McNicol says, adding the tank holds "about 3.6 million gallons of chilled water that we generate and store and push back to the campus. The North Plant that really charges the tank has two 2,000-ton (chillers) in it.

"In 2008, we got into the Central Energy Plant and took those older machines offline. Some of them had the refrigerant changes. We had made the conversion, but they still weren't the most energy-efficient yet. So we replaced them with two 2,000-ton units."

McNicol says the decision to specify the particular chillers for the Central Energy Plant was based on the efficiency of the new units and the manufacturer's service history. The purchase included a 10-year warranty for maintenance and repair.

The chiller replacement started in December 2007 and finished in August 2008, McNicol says, adding that because most of the project was done over the winter, the North Energy Plant was able to meet the campus's cooling load.

"We started the project in the winter to minimize the cooling effect on the campus," he says. "By the time we needed a chiller for the summer (of 2008), one chiller was ready to run, and the other one followed soon thereafter."

The university system's Office of Planning and Construction handled the engineering and contracting, and local plant personnel assisted as needed in shutdowns and startups. McNicol's department consists of 10 employees: a manager, supervisor, three maintenance technicians, and five operators. The department is responsible for the operations and maintenance of the two main plants that provide the heating and cooling for the campus, including maintaining their distribution systems.




Project Profile: Cooling Challenge

Part 1: Campus Expansion Creates Challenges for Chillers

Part 2: Replacing Chiller on College Campus Requires Ample Planning

Part 3: Energy Efficiency: Beyond Chiller Replacement


Comments


Browse Articles

On FacilitiesNet: cooling facilities, meeting hvac demands, chiller replacement

FaciliyZone

Search for cooling facilities, meeting hvac demands, chiller replacement articles on FacilityZone

Find us on Google+
Modine. Learn more.
Leading the way in high efficiency boilers and water heaters. Aerco, click here.


QUICK Sign-up - Membership Includes:

New Content and Magazine Article Updates
Educational Webcast Alerts
Building Products/Technology Notices
Complete Library of Reports, Webcasts, Salary and Exclusive Member Content



click here for more member info.